Description
EATON PDE33G0320VAAS
EATON PDE33G0320VAAS
PDE33F0320VAAS – Circuit breaker, 320A, 25kA, 3p, 50°C, screw terminal
TECHNICAL DATA
General
Standards
IEC/EN 60947
Ambient temperatureAmbient temperature, storage
– 20 – + 70 °C
Ambient temperatureOperation
-20 – +70 °C
Direction of incoming supply
Vertical and 90° in all directions
Degree of protectionDevice
IP2X with finger guard accessories
Circuit-breakers
Rated current = rated uninterrupted current [In = Iu]
320 A
Rated surge voltage invariability [Uimp ]Main contacts
8000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
4000 V
Rated operational voltage [Ue]
440 V AC
Rated operational voltage [Ue]
250 V DC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
800 V
Product range
Circuit-breaker
Protective function
System and cable protection
Standard/Approval
IEC
Installation type
Fixed
Release system
Thermomagnetic release
Construction size
PDE3
Description
thermally adjustable, magnetically adjustable; calibrated at 50°C
Number of poles
3 pole
Standard equipment
Screw connection
Switching capacity
400/415 V 50 Hz [Icu ]
25 kA
TECHNICAL DATA
General
Standards
IEC/EN 60947
Ambient temperatureAmbient temperature, storage
– 20 – + 70 °C
Ambient temperatureOperation
-20 – +70 °C
Direction of incoming supply
Vertical and 90° in all directions
Degree of protectionDevice
IP2X with finger guard accessories
Circuit-breakers
Rated current = rated uninterrupted current [In = Iu]
320 A
Rated surge voltage invariability [Uimp ]Main contacts
8000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
4000 V
Rated operational voltage [Ue]
440 V AC
Rated operational voltage [Ue]
250 V DC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
800 V
Switching capacity
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]240 V 50/60 Hz [Icu ]
35 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]400/415 V 50 Hz [Icu ]
25 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]440 V 50/60 Hz [Icu ]
20 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]230 V 50/60 Hz [Ics ]
35 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]400/415 V 50/60 Hz [Ics ]
25 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]440 V 50/60 Hz [Ics ]
15 kA
Utilization category to IEC/EN 60947-2
A
Lifespan, mechanical [Operations]
15000
Lifespan, electricalMax. operating frequency
60 Ops/h
Reviews
There are no reviews yet.