Description
SICK UE23-2MF2D3
SICK UE23-2MF2D3
- Safety technology parameters
Integration level for security SILCL2 (EN 62061) Category Category 3 (EN ISO 13849) performance level PL d (EN ISO 13849) B 10d -value 5.45 x 10 4 Wiring diagram (AC-15, 230 V, I = 3 A) 1.26 x 10 6 Wiring diagram (AC-15, 230 V, I = 1.5 A)
5.9 x 10 6 Wiring diagram (AC-15, 230 V, I = 0.75 A)
4.35 x 10 5 Wiring diagram (DC-13, 24 V, I = 2.5 A)
1 x 10 7 Wiring diagram (DC-13, 24 V, I = 0.63 A)
PFH D (average probability of dangerous outage per hour) 3.0 x 10 -6 (EN ISO 13849) T M (lifetime) 20 years (EN ISO 13849) Stop category 0 (EN 60204-1)
- Interfaces
Connection type Fixed screw connections Number of acknowledgment current paths (NO contact) 2, safety related
- Electrical data – Operating data
Protection class II safe separation (EN 50178) Voltage source U v A1, A2 24 V DC (19,2 V DC … 30 V DC) Signal transport (≤ 2,4 Vss) 1) Power consumption (≤ 1 W) Overvoltage category III Rated insulation voltage Ui 300 V AC Rated impulse voltage strength U imp 6 kV Test voltage 3.5 kV (50 Hz) (EN 60439-1) - 1) In DC operation, within the limits of U E.
- Electrical data – Control voltage: Y1-Y2-Y3
Control voltage UV – 2 V DC … UV control current ≤ 20 mA short circuit current ≤ 250 mA Short circuit protection PTC-Resistance rollback time Manuel ≤ 70 ms Automatic ≤ 600 ms

SICK UE23-2MF2D3
Reviews