Description
SCHMERSAL SRB301LC 24VAC-DC
SCHMERSAL SRB301LC 24VAC-DC
SCHMERSAL SAFETY RELAY
- 1 Signalling output
- 3 safety contacts, STOP 0
- Suitable for signal processing of potentialfree outputs, e.g. emergency stop command devices, position switches and solenoid interlocks
Ordering data
Replacement article number 101165472
Product type description SRB301LC-24V
Article number (order number) 101163475
EAN (European Article Number) 4250116201532
eCl@ss number, version 12.0 27-37-18-19
eCl@ss number, version 11.0 27-37-18-19
eCl@ss number, version 9.0 27-37-18-19
ETIM number, version 7.0 EC001449
ETIM number, version 6.0 EC001449
Available until 31.12.2024
Approvals – Standards
Certificates TÜV
cULus
CCC
EAC
TILVA
General data
Standards EN IEC 62061
EN ISO 13849-1
EN IEC 60947-5-1
EN IEC 60947-5-3
EN IEC 60947-5-5
EN IEC 61508
EN IEC 60204-1
EN IEC 60947-1
Climatic stress EN 60068-2-78
Enclosure material Glass-fibre reinforced thermoplastic, ventilated
Material of the contacts, electrical AgSn0. self-cleaning, positive drive
Gross weight 250 g
General data – Features
Stop-Category 0
Wire breakage detection Yes
Cross-circuit detection Yes
Start input Yes
Feedback circuit Yes
Automatic reset function Yes
Earth connection detection Yes
Integral system diagnostics, status Yes
Number of auxiliary contacts 1
Number of LEDs 4
Number of normally closed (NC) 2
Number of safety contacts 3
Safety classification Standards EN IEC 60947-5-1
EN IEC 61508
Safety classification – Relay outputs Performance Level, stop 0, up to e
Category, Stop 0 4
Diagnostic Coverage (DC) Level, Stop 0 ≥ 99 %
PFH value, Stop 0 2.00 x 10⁻⁸ /h
Safety Integrity Level (SIL), Stop 0, suitable for applications in 3
Mission time 20 Year(s)
Common Cause Failure (CCF), minimum 65
Mechanical data
Mechanical life, minimum 10,000,000 Operations
Mounting Snaps onto standard DIN rail to EN 60715
Mechanical data – Connection technique
Termination rigid or flexible
Screw terminals M20 x 1.5
Terminal designations IEC/EN 60947-1
Cable section, minimum 0.25 mm²
Cable section, maximum 2.5 mm²
Tightening torque of Clips 0.6 Nm
Mechanical data – Dimensions
Width 22.5 mm
Height 100 mm
Depth 121 mm
Ambient conditions
Degree of protection of the enclosure IP40
Degree of protection of the mounting space IP54
Degree of protection of clips or terminals IP20
Ambient temperature, minimum -25 °C
Ambient temperature, maximum +45 °C
Storage and transport temperature, minimum -40 °C
Storage and transport temperature, maximum +85 °C
Resistance to vibrations 10…55 Hz, Amplitude 0.35 mm, ± 15 %
Restistance to shock 30 g / 11 ms
Ambient conditions – Insulation values
Rated impulse withstand voltage Uimp 4 kV
Overvoltage category III
Degree of pollution 2
Electrical data
Frequency range 50 Hz
60 Hz
Rated operating voltage 24 VAC -15% / +10%
24 VDC -15%/+20%, residual ripple max. 10%
Rated AC voltage for controls, 50 Hz, minimum 20.4 VAC
Rated control voltage at AC 50 Hz, maximum 26.4 VAC
Rated AC voltage for controls, 60 Hz, minimum 20.4 VAC
Rated control voltage at AC 60 Hz, maximum 26.4 VAC
Rated AC voltage for controls at DC minimum 20.4 VDC
Rated control voltage at DC, maximum 28.8 VDC
Electrical power consumption 1.7 W
Electrical power consumption 1.9 VA
Contact resistance, maximum 0.1 Ω
Note (Contact resistance) in new state
Drop-out delay in case of power failure, typically 80 ms
Drop-out delay in case of emergency, typically 20 ms
Pull-in delay at automatic start, maximum, typically 100 ms
Pull-in delay at RESET, typically 20 ms
Electrical data – Safe relay outputs
Voltage, Utilisation category AC-15 230 VAC
Current, Utilisation category AC-15 6 A
Voltage, Utilisation category DC-13 24 VDC
Current, Utilisation category DC-13 6 A
Switching capacity, minimum 10 VDC
Switching capacity, minimum 10 mA
Switching capacity, maximum 250 VAC
Switching capacity, maximum 8 A
Electrical data – Digital inputs
Conduction resistance, maximum 40 Ω
Electrical data – Digital Output
Voltage, Utilisation category DC-12 24 VDC
Current, Utilisation category DC-12 0.1 A
Electrical data – Relay outputs (auxiliary contacts)
Switching capacity, maximum 24 VDC
Switching capacity, maximum 2 A
Electrical data – Electromagnetic compatibility (EMC)
EMC rating EMC-Directive
Status indication
Indicated operating states Position relay K2
Position relay K1
Internal operating voltage Ui
Other data
Note (applications) Guard system
Emergency-Stop button
Pull-wire emergency stop switches
Note
Note (General) Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Wiring example
Note (Wiring diagram) The wiring diagram is shown with guard doors closed and in de-energised condition.
Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts.
Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X2. If the feedback circuit is not required, establish a bridge.
The control recognises cross-short, cable break and earth leakages in the monitoring circuit.
Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R); cross-wire monitoring and feedback circuit (H2)
In case of a 1-channel control, connect the NC contact to the operating voltage and bridge S11/S12 and S21/S22.
SCHMERSAL SRB301LC 24VAC-DC