Description
SCHMERSAL AES 1112
SCHMERSAL AES 1112
SCHMERSAL SAFETY RELAY
- Monitoring of BNS range magnetic safety sensors
- 1 safety contact, STOP 0
Ordering data
Product type description | AES 1112 24 VDC |
Article number (order number) | 101128982 |
EAN (European Article Number) | 4030661059259 |
eCl@ss number, version 12.0 | 27-37-18-19 |
eCl@ss number, version 11.0 | 27-37-18-19 |
eCl@ss number, version 9.0 | 27-37-18-19 |
ETIM number, version 7.0 | EC001449 |
ETIM number, version 6.0 | EC001449 |
Approvals – Standards
Certificates | BG cULus EAC |
General data
Standards | BG-GS-ET-14 BG-GS-ET-20 EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress | EN 60068-2-3 BG-GS-ET-14 |
Enclosure material | Glass-fibre reinforced thermoplastic, ventilated |
Material of the contacts, electrical | AgCdO |
Gross weight | 122 g |
General data – Features
Stop-Category | 0 |
Wire breakage detection | Yes |
Automatic reset function | Yes |
Reset after disconnection of supply voltage | Yes |
Integral system diagnostics, status | Yes |
Number of LEDs | 1 |
Number of normally closed (NC) | 2 |
Number of normally open (NO) | 1 |
Number of safety contacts | 1 |
Safety classification |
Standards | EN ISO 13849-1 EN IEC 61508 |
Safety classification – Relay outputs |
Performance Level, up to | c |
Category | 1 |
PFH value | 1.14 x 10⁻⁶ /h |
Notice | for max. 50,000 switching cycles/year and max. 80% contact load |
Safety Integrity Level (SIL), suitable for applications in | 1 |
Mission time | 20 Year(s) |
Mechanical data
Mechanical life, minimum | 10,000,000 Operations |
Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data – Connection technique
Termination | rigid or flexible Screw terminals M20 x 1.5 |
Terminal designations | IEC/EN 60947-1 |
Cable section, maximum | 2.5 mm² |
Tightening torque of Clips | 0.6 Nm |
Mechanical data – Dimensions
Width | 22.5 mm |
Height | 75 mm |
Depth | 110 mm |
Ambient conditions
Degree of protection of the enclosure | IP40 |
Degree of protection of the mounting space | IP54 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature, minimum | +0 °C |
Ambient temperature, maximum | +55 °C |
Storage and transport temperature, minimum | -25 °C |
Storage and transport temperature, maximum | +70 °C |
Resistance to vibrations | 10…55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
Ambient conditions – Insulation values
Rated impulse withstand voltage Uimp | 4 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Electrical data
Frequency range | 50 Hz 60 Hz |
Thermal test current | 4 A |
Rated operating voltage | 24 VDC ± 15 % |
Rated AC voltage for controls at DC minimum | 20.4 VDC |
Rated control voltage at DC, maximum | 27.6 VDC |
Electrical power consumption | 2.4 W |
Contact resistance, maximum | 0.1 Ω |
Note (Contact resistance) | in new state |
Drop-out delay in case of power failure, typically | 80 ms |
Drop-out delay in case of emergency, typically | 20 ms |
Pull-in delay at automatic start, maximum, typically | 100 ms |
Pull-in delay at RESET, typically | 20 ms |
Electrical data – Safe relay outputs
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 3 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 2 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 8 A |
Electrical data – Digital inputs
Conduction resistance, maximum | 40 Ω |
Electrical data – Digital Output
Voltage, Utilisation category DC-12 | 24 VDC |
Current, Utilisation category DC-12 | 0.1 A |
Electrical data – Relay outputs (auxiliary contacts)
Switching capacity, maximum | 24 VDC |
Switching capacity, maximum | 2 A |
AES 1112 SCHMERSAL
Reviews