Description
EATON PKZM4-63 EA
EATON PKZM4-63 EA
Motor – Protective Circuit – Breaker , Ir= 55 – 65 A, Screw terminals, Terminations: IP00
General
Standards
IEC/EN 60947, VDE 0660,UL, CSA
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureStorage
– 40 – 80 °C
Ambient temperatureOpen
-25 – +55 °C
Ambient temperatureEnclosed
– 25 – 40 °C
Direction of incoming supply
as required
Degree of protectionDevice
IP20
Degree of protectionTerminations
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
15 g
Altitude
Max. 2000 m
Terminal capacity main cableScrew terminalsSolid
1 x (0.75 – 16)
2 x (0.75 – 16) mm2
2 x (0.75 – 16) mm2
Terminal capacity main cableScrew terminalsFlexible with ferrule to DIN 46228
1 x (0.75 – 35)
2 x (0.75 – 25) mm2
2 x (0.75 – 25) mm2
Terminal capacity main cableScrew terminalsSolid or stranded
14 – 1 AWG
Terminal capacity main cableScrew terminalsStripping length
14 mm
Specified tightening torque for terminal screwsMain cable
3.3 Nm
Product range
PKZM4 motor protective circuit-breakers up to 65 A
Basic function
Motor protection
Notes
Also suitable for motors with efficiency class IE3.
Connection technique
Screw terminals
Max. motor rating
AC-3220 V 230 V 240 V [P]
18.5 kW
AC-3380 V 400 V 415 V [P]
34 kW
AC-3440 V [P]
37 kW
AC-3500 V [P]
45 kW
AC-3660 V 690 V [P]
55 kW
Rated uninterrupted current [Iu]
65 A
Setting range
Phase-failure sensitivity
IEC/EN 60947-4-1, VDE 0660 Part 102
Notes
Overload trigger: tripping class 10 A
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
TECHNICAL DATA
General
Standards
IEC/EN 60947, VDE 0660,UL, CSA
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureStorage
– 40 – 80 °C
Ambient temperatureOpen
-25 – +55 °C
Ambient temperatureEnclosed
– 25 – 40 °C
Direction of incoming supply
as required
Degree of protectionDevice
IP20
Degree of protectionTerminations
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
15 g
Altitude
Max. 2000 m
Terminal capacity main cableScrew terminalsSolid
1 x (0.75 – 16)
2 x (0.75 – 16) mm2
2 x (0.75 – 16) mm2
Terminal capacity main cableScrew terminalsFlexible with ferrule to DIN 46228
1 x (0.75 – 35)
2 x (0.75 – 25) mm2
2 x (0.75 – 25) mm2
Terminal capacity main cableScrew terminalsSolid or stranded
14 – 1 AWG
Terminal capacity main cableScrew terminalsStripping length
14 mm
Specified tightening torque for terminal screwsMain cable
3.3 Nm
Main conducting paths
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated operational voltage [Ue ]
690 V AC
Rated uninterrupted current = rated operational current [Iu = Ie ]
65 A
Rated frequency [f]
50/60 Hz
Current heat loss (3 pole at operating temperature)
33,5 W
Impedance per pole
2 mΩ
Lifespan, mechanical [Operations]
0.03 x 106
Lifespan, electrical (AC-3 at 400 V)Lifespan, electrical [Operations]
0.03 x 106
Max. operating frequency
40 Ops/h
Short-circuit ratingDCShort-circuit rating
60 kA
Short-circuit ratingDCNotes
up to 250 V
Motor switching capacityAC-3 (up to 690V)
65 A
Motor switching capacityDC-5 (up to 250V)
63 (3 contacts in series) A
Trip blocks
Temperature compensationto IEC/EN 60947, VDE 0660
– 5…40 °C
Temperature compensationOperating range
– 25…55 °C
Temperature compensation residual error for T > 40 °C
≦ 0.25 %/K
Setting range of overload releases
0.6 – 1 x Iu
short-circuit release
Basic device, fixed: 15.5 x Iu
Short-circuit release tolerance
± 20%
Phase-failure sensitivity
IEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacityMaximum motor ratingThree-phase460 V
480 V
480 V
40 HP
Switching capacityMaximum motor ratingThree-phase575 V
600 V
600 V
50 HP
Short Circuit Current Rating, type E240 V
50 kA
Short Circuit Current Rating, type E480 Y / 277 V
50 kA
Short Circuit Current Rating, type EAccessories required
BK50/3-PKZ4-E
Short Circuit Current Rating, group protection600 V High FaultSCCR (fuse)
42 kA
Short Circuit Current Rating, group protection600 V High Faultmax. Fuse
600 A
Short Circuit Current Rating, group protection600 V High FaultSCCR (CB)
42 kA
Short Circuit Current Rating, group protection600 V High Faultmax. CB
600 A