Description
EATON PDE13G0160TAAJ
EATON PDE13G0160TAAJ
PDE13G0160TAAJ – Circuit breaker, 160A, 36kA, 3p, box terminal
General
Standards
IEC/EN 60947
Ambient temperatureAmbient temperature, storage
– 20 – + 70 °C
Ambient temperatureOperation
-20 – +70 °C
Direction of incoming supply
Vertical and 90° in all directions
Degree of protectionDevice
IP2X with finger guard accessories
Circuit-breakers
Rated current = rated uninterrupted current [In = Iu]
160 A
Rated surge voltage invariability [Uimp ]Main contacts
6000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
440 V AC
Rated operational voltage [Ue]
250 V DC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
800 V
Switching capacity
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]240 V 50/60 Hz [Icu ]
50 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]400/415 V 50 Hz [Icu ]
36 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]440 V 50/60 Hz [Icu ]
30 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]230 V 50/60 Hz [Ics ]
50 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]400/415 V 50/60 Hz [Ics ]
36 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]440 V 50/60 Hz [Ics ]
22.5 kA
Utilization category to IEC/EN 60947-2
A
Lifespan, mechanical [Operations]
25000
Lifespan, electricalMax. operating frequency
120 Ops/h
Terminal capacity
Standard equipment
Box terminal
Reviews