Description
EATON PDE13G0080TAAJ
EATON PDE13G0080TAAJ
PDE13G0080TAAJ – Circuit breaker, 80A, 36kA, 3p, box terminal.
TECHNICAL DATA
General
Standards
IEC/EN 60947
Ambient temperatureAmbient temperature, storage
– 20 – + 70 °C
Ambient temperatureOperation
-20 – +70 °C
Direction of incoming supply
Vertical and 90° in all directions
Degree of protectionDevice
IP2X with finger guard accessories
Circuit-breakers
Rated current = rated uninterrupted current [In = Iu]
80 A
Rated surge voltage invariability [Uimp ]Main contacts
6000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
440 V AC
Rated operational voltage [Ue]
250 V DC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
800 V
Product range
Circuit-breaker
Protective function
System and cable protection
Standard/Approval
IEC
Installation type
Fixed
Release system
Thermomagnetic release
Construction size
PDE1
Description
thermally adjustable, magnetically adjustable; calibrated at 40°C
Number of poles
3 pole
Standard equipment
Box terminal
Switching capacity
400/415 V 50 Hz [Icu ]
36 kA
EATON PDE13G0080TAAJ
TECHNICAL DATA
General
Standards
IEC/EN 60947
Ambient temperatureAmbient temperature, storage
– 20 – + 70 °C
Ambient temperatureOperation
-20 – +70 °C
Direction of incoming supply
Vertical and 90° in all directions
Degree of protectionDevice
IP2X with finger guard accessories
Circuit-breakers
Rated current = rated uninterrupted current [In = Iu]
80 A
Rated surge voltage invariability [Uimp ]Main contacts
6000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
440 V AC
Rated operational voltage [Ue]
250 V DC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
800 V
Switching capacity
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]240 V 50/60 Hz [Icu ]
50 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]400/415 V 50 Hz [Icu ]
36 kA
Rated short-circuit breaking capacity Icn [Icn ]Icu to IEC/EN 60947 test cycle O-t-CO [Icu]440 V 50/60 Hz [Icu ]
30 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]230 V 50/60 Hz [Ics ]
50 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]400/415 V 50/60 Hz [Ics ]
36 kA
Rated short-circuit breaking capacity Icn [Icn ]Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]440 V 50/60 Hz [Ics ]
22.5 kA
Utilization category to IEC/EN 60947-2
A
Lifespan, mechanical [Operations]
25000
Lifespan, electricalMax. operating frequency
120 Ops/h
Terminal capacity
Standard equipment
Box terminal
DESIGN VERIFICATION AS PER IEC/EN 61439
Operating ambient temperature min.
-20 °C
Operating ambient temperature max.
+70 °C
TECHNICAL DATA ETIM 8.0
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection (ecl@ss10.0.1-27-37-04-09 [AJZ716013])
Rated permanent current Iu
80 A
Rated voltage
220 – 440 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36 kA
Overload release current setting
64 – 80 A
Adjustment range short-term delayed short-circuit release
0 – 0 A
Adjustment range undelayed short-circuit release
800 – 800 A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Frame clamp
Device construction
Complete device in housing