WEIDMULLER ACT20P-CML-10-AO-RC-S
WEIDMULLER ACT20P-CML-10-AO-RC-S
Version | Current-measuring transducer, Limit value monitoring, Input : 0…1/5/10 A, Analogue output, Relay output, Terminal connection |
Order No. | 2044850000 |
Type | ACT20P-CML-10-AO-RC-S |
GTIN (EAN) | 4050118409680 |
Qty. | 1 pc(s). |
Depth | 113.6 mm |
Depth (inches) | 4.472 inch |
Height | 119.2 mm |
Height (inches) | 4.693 inch |
Width | 17.5 mm |
Width (inches) | 0.689 inch |
Net weight | 141 g |
Storage temperature | -40 °C…85 °C |
Operating temperature | -25 °C…60 °C |
Operating temperature, min. | -25 °C |
Operating temperature, max. | 60 °C |
Humidity | 5…95 %, no condensation |
Input frequency | AC: 15…400 Hz (true root mean square) |
Input measurement range | configurable, 0…1/5/10 A AC (RMS) or DC, max. peak current 10 × IInput (1 s), , For DC current measurement (AA): Current direction display at the output (-/+ analog value) |
Number of inputs | 1 |
Load impedance current | ≤ 600 Ω |
Type | active, connected control must be passive |
Alarm function | Surge current, Under-current, Alarm delay: 0…10 s |
Max. switching voltage, AC | 250 V |
Max. switching voltage, DC | 24 V |
Number of digital outputs | 1 |
Rated switching current | 2 A |
Type | Relay, 1 CO contact, normal / inverse adjustment |
Load resistance current | ≤ 600 Ω |
Load resistance voltage | ≥ 10 kΩ |
Number of analogue outputs | 1 |
Output current | Adjustable, 0…20 mA, 4…20 mA, -20…+20 mA |
Output voltage | Adjustable, 0…10 V, 2…10 V, 0…5 V, 1…5 V, -5…+5 V, -10…+10 V |
Transmit function | direct or inverted |
Type (analogue output) | Voltage and current output (configurable) |